EE35T - Example of an Insulation Coordination


The Figure of the Substation may be found here.

This system shows a 132kV incoming feeder, which is connected to a 132/66kV transformer at the substation. The arrester is place between the feeder and the transformer.

It should be noted that the rating of the arrester is 120kV. Since the system is 132kV, and a tolerance of 10% is assumed, then the maximum voltage that the system can experience is

132kV * 1.1 = 145200V.

However, the system is effectively earthed (via the arrester) and for an effectively earthed system, the maximum arrester voltage is 80% of the system voltage. Thus,

Normal Arrester voltage = 145200 * 0.8 = 120000 = 120kV.
 

If a lightning strike occurs on the incoming feeder, three scenarios are possible.

1st Scenario: Impulse voltage of lightning strike is less than the Discharge Voltage of the Arrester

2nd Scenario: Impulse Voltage of lightning strike is less than BIL of arrester, but greater than Discharge Voltage 3rd Scenario: Impulse Voltage of lightning strike is greater than the BIL of arrester