The First Step in designing a Substation is to design an Earthing and Bonding System.
Earthing and Bonding
The function of an earthing and bonding system is to provide an earthing system connection to which transformer neutrals or earthing impedances may be connected in order to pass the maximum fault current. The earthing system also ensures that no thermal or mechanical damage occurs on the equipment within the substation, thereby resulting in safety to operation and maintenance personnel. The earthing system also guarantees eqipotential bonding such that there are no dangerous potential gradients developed in the substation.
In designing the substation, three voltage have to be considered.
1. Touch Voltage: This is the difference
in potential between the surface potential and the potential at an earthed
equipment whilst a man is standing and touching the earthed structure.
2. Step Voltage: This is the potential
difference developed when a man bridges a distance of 1m with his feet
while not touching any other earthed equipment.
3. Mesh Voltage: This is the maximum
touch voltage that is developed in the mesh of the earthing grid.
Substation Earthing Calculation Methodology
Calculations for earth impedances and touch and step potentials are based on site measurements of ground resistivity and system fault levels. A grid layout with particular conductors is then analysed to determine the effective substation earthing resistance, from which the earthing voltage is calculated.
In practice, it is normal to take the highest fault level for substation earth grid calculation purposes. Additionally, it is necessary to ensure a sufficient margin such that expansion of the system is catered for.
To determine the earth resistivity, probe tests are carried out on the site. These tests are best performed in dry weather such that conservative resistivity readings are obtained.
Earthing Materials
1. Conductors: Bare copper conductor
is usually used for the substation earthing grid. The copper bars themselves
usually have a cross-sectional area of 95 square millimetres, and they
are laid at a shallow depth
of 0.25-0.5m, in 3-7m squares. In addition to the buried potential earth
grid, a separate above ground
earthing ring is usually provided, to which all metallic substation plant
is bonded.
2. Connections: Connections to the
grid and other earthing joints should not be soldered because the heat
generated
during fault conditions could cause a soldered joint to fail. Joints are
usually bolted, and in this case, the
face of the joints should be tinned.
3. Earthing Rods: The earthing grid
must be supplemented by earthing rods to assist in the dissipation of earth
fault
currents and further reduce the overall substation earthing resistance.
These rods are usually made of
solid copper, or copper clad steel.
4. Switchyard Fence
Earthing: The switchyard fence earthing practices are possible
and are used by different utilities. These are:
(i) Extend the substation earth grid 0.5m-1.5m beyond the fence perimeter.
The fence is then
bonded to the grid at regular intervals.
(ii) Place the fence beyond the perimeter of the switchyard earthing grid
and bond the fence to its
own earthing rod system. This earthing rod system is not coupled to the
main substation earthing
grid.
Layout of Substation
The layout of the substation is very important since there should be a Security of Supply. In an ideal substation all circuits and equipment would be duplicated such that following a fault, or during maintenance, a connection remains available. Practically this is not feasible since the cost of implementing such a design is very high. Methods have been adopted to achieve a compromise between complete security of supply and capital investment. There are four categories of substation that give varying securities of supply:
Different Layouts for Substations
Single Busbar
The general schematic for such a substation is shown in the figure below.
With this design, there is an ease of operation of the substation. This design also places minimum reliance on signalling for satisfactory operation of protection. Additionally there is the facility to support the economical operation of future feeder bays.
Such a substation has the following characteristics.
The general layout for a full mesh substation
is shown in the schematic below.
The characteristics of such a substation are as follows.
The layout of a 1 1/2 circuit breaker substation
is shown in the schematic below.
The reason that such a layout is known as a 1 1/2 circuit breaker is
due to the fact that in the design, there are 9 circuit breakers that are
used to protect the 6 feeders. Thus, 1 1/2 circuit breakers protect 1 feeder.
Some characteristics of this design are:
Principle of Substation Layouts
Substation layout consists essentially in arranging a number of switchgear components in an ordered pattern governed by their function and rules of spatial separation.
Spatial Separation
Two methods are available for separating equipment in a maintenance zone that has been isolated and made dead.
1. The provision of a section clearance
2. Use of an intervening earthed barrier
The choice between the two methods depends on the voltage and whether horizontal or vertical clearances are involved.
Separation by earthed barrier = Earth Clearance + 50mm for barrier + Earth Clearance
Separation by section clearance = 2.44m + Earth clearance
Establishing Maintenance Zones
Some maintenance zones are easily defined and
the need for them is self evident as is the case of a circuit breaker.
There should be a means of isolation on each side of the circuit breaker,
and to separate it from adjacent live parts, when isolated, either by section
clearances or earth barriers.
Electrical Separations
1. Between the terminals of the busbar isolator
and their connections.
2. Between the terminals of the circuit breaker
and their connections.
3. Between the terminals of the feeder isolator
and their connections.
Components of a Substation
The substation components will only be considered to the extent where they influence substation layout.
Circuit Breakers
There are two forms of open circuit breakers:
1. Dead Tank - circuit breaker compartment is
at earth potential.
2. Live Tank - circuit breaker compartment is
at line potential.
The form of circuit breaker influences the way in which the circuit breaker is accommodated. This may be one of four ways.
CT's may be accommodated in one of six manners:
Isolators
These are essentially off load devices although they are capable of dealing with small charging currents of busbars and connections. The design of isolators is closely related to the design of substations. Isolator design is considered in the following aspects:
Conductor Systems
An ideal conductor should fulfil the following requirements:
In an effort to make the conductor ideal, three different types have been utilized, and these include:
Insulation
Insulation security has been rated very highly
among the aims of good substation design. Extensive research is done on
improving flashover characteristics as well as combating pollution. Increased
creepage length, resistance glazing, insulation greasing and line washing
have been used with varying degrees of success.
Power Transformers
EHV power transformers are usually oil immersed with all three phases in one tank. Auto transformers can offer advantage of smaller physical size and reduced losses. The different classes of power transformers are:
Transformers that are located and a cell should
be enclosed in a blast proof room.
Overhead Line Terminations
Two methods are used to terminate overhead lines at a substation.
The following clearances should be observed:
|
|
MINIMUM GROUND CLEARANCE |
|
|
|
|
|
|
|
|
|
|
|
|